3.6 Power Out Connections
1. Remove the protective cover from the terminal block.
2. A factory jumper has been added to connect NEUTRAL to GROUND.
If the front connector requires LINE and NEUTRAL to be reversed, move
this jumper to connect LINE to GROUND. See Figure 3–7 below. Most loads
require NEUTRAL to be grounded.
The factory jumper may be removed if the load has a GROUND or if LINE or
NEUTRAL voltages are held to less than 500 VRMS with respect to chassis.
3. Reinstall the protective cover on the terminal block.
WARNING! Verify that the load is set up to be LINE GROUNDED
or NEUTRAL GROUNDED. (Equipment with polarized plugs
requires NEUTRAL to be grounded.)
Figure 3–7 Output Power Connections